Payment Terms : T/T
Secondary Side Supply Water : 40
Filtration Accuracy : 50 / 25
Model Number : DWW2400-125A
Primary Side Supply Water : 36
MOQ : 1
Delivery Time : 5-8 weeks
Dimensions : 900*1200*2200
Secondary Side Connection : DN125
Packaging Details : Cartons
Brand Name : Hailos
Power Supply : AC 3/N/PE 380~480V 50/60Hz DC 800V
Place of Origin : China
Price : $10000~$50000
Secondary Side Flow Rate : 180
Supply Ability : 500sets /month
Cooling capacity : 2400kW
Certification : ISO、CE
| Parameter | Unit | DWW300-65A | DWW600-80AW | DWW600-80AN | DWW1200-100A | DWW2400-125A |
| Cooling Capacity | kW | 300 | 600 | 600 | 1,200 | 2,400 |
| Secondary Side Supply Water | ℃ | 40 | ||||
| Secondary Side Flow Rate | m³/h | 26 | 52 | 52 | 90 | 180 |
| Secondary Side Connection | DN | DN65 | DN80 | DN80 | DN100 | DN125 |
| ATD | ℃ | 5 | 5 | 4 | 4 | 4 |
| Filtration Accuracy | μm | 50 | 50 | 50 / 25 | 50 / 25 | 50 / 25 |
| Secondary Side External Output Pressure Difference | kPa | ≥120 | ≥120 | ≥120 | ≥120 | ≥120 |
| Number of Pumps | N/A | 1+1 redundancy | 1+1 redundancy | 1+1 redundancy | 1+1 redundancy | 2+1 redundancy |
| Primary Side Supply Water | ℃ | 35 | 35 | 36 | 36 | 36 |
| Primary Side Flow Rate | m³/h | 26 | 52 | 52 | 90 | 180 |
| Primary Side Connection | DN | DN50 | DN80 | DN80 | DN100 | DN125 |
| Rated Power | kW | 4.5 | 8 | 10.5 | 22.5 | 44.5 |
| Primary Side Pressure Drop | kPa | ≤100 | ≤100 | ≤120 | ≤150 | ≤150 |
| Power Supply | / | AC 3/N/PE 380~480V 50/60HZ DC 800V |
||||
| Unit Dimensions - Width | mm | 600 | 900 | 600 | 600 | 900 |
| Unit Dimensions - Depth | mm | 1200 | ||||
| Unit Dimensions - Height | mm | 2,000 | 2,000 | 2,000 | 2,200 | 2,200 |





Project Case

A3: Yes, warm welcome customers to visit our workshop and test equipment on site. We support live video factory tour if you cannot come to China temporarily.
|
|
Rack-Mounted Coolant Distribution Unit CDU 300-2400kW Liquid Cooling for Data Center Images |